Installation Instructions

Document No. 553-130
Installation Instructions
August 31, 2013
Page 2 of 6 Siemens Industry, Inc.
CAUTION:
Anchorage is not preapproved for Seismic
Certification and must be approved by the
Inspector of Record before installation.
Seismic Certification Preapproval requires:
Installed Equipment is listed in OSP.
Enclosures are non-isolated wall
mounted using four 1/4” minimum
diameter bolts.
Enclosure assembly certification
includes enclosure with door, service
box, installed equipment and wiring.
Total assembly weight not to exceed
50 lbs. for 19” enclosure assembly or
100 lbs. for 34” enclosure assembly.
Center of gravity is located from origin
at enclosure lower left mounting hole
to 9 x 8 x 2 inches for 19” assembly or
10 x 16 x 2.5 inches for 34” assembly.
Variance due to installed components
is < 10%.
DIN Rails mounted on backplane
using three supplied screws each.
Listed equipment not capable of being
installed on DIN rails may be fastened
to the backplane with supplied screws.
Listed communication devices may be
fastened to enclosure or backplane
and power packs to outlet with 3M
®
Dual Lock
®
Reclosable Fasteners
SJ3560 (Type 250). Use two pair for
devices and one pair for power packs.
Minimum 1” square per 2 lbs.
PXC0048R1
I
Figure 1. 19” PX Series Enclosure Assembly.
PXC0047R1
I
Figure 2. 34” PX Series Enclosure Assembly.