Installation Instructions

Installation Instructions
Document No. 553-130
August 31, 2013
19” and 34” PX Series Enclosure
Assemblies
Item Number: 553-130, Rev.
DA
Page 1 of 6
Product Description
The 19” and 34” PX series enclosures (see Figure 1
and Figure 2) are UL Smoke Control listed for indoor
use to:
provide a degree of protection to personnel
against incidental contact with the enclosed
Siemens Building Control devices
provide a degree of protection for those
devices against falling dirt
The 19” and 34” PX series enclosures are factory-
equipped with the following:
Factory-installed backplane assembly, which
includes wire tie down rails and DIN rails
Mounting features for PX series service box
Removable hinged door with key lock and
label pouch
Conduit knockouts and venting
The 19” and 34” PX series enclosures, when
installed per this instruction, are certified to comply
with IBC 2009 and CBC 2010 and may be used with
following List of Equipment/Components with
OSHPD Special Seismic Certification Preapproval
(OSP)
OSP-217-10 and OSP-218-10
Product Numbers
PXA-ENC34 34” PX Series Enclosure Assembly
PXA-ENC19 19” PX Series Enclosure Assembly
See Figures 4 and 5 for enclosure dimensions.
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedure as
specified.
Expected Installation Time
30 minutes
Required Tools and Materials
Adjustable wrench or pliers
Electric drill
Punch
Hammer
Level
Marker
Screwdrivers, small and medium Phillips
Tape measure
Tie-wraps
Wire stripper/side cutters
Four corrosion resistant 1/4” - 20 Bolts, flat
washers and nuts
To mount on concrete or masonry:
Hammer drill
1/2 inch carbide tipped masonry bit
Four 1/4-20 corrosion resistant wall anchors
Prerequisites
CAUTION:
Do not mount the enclosure on ductwork,
HVAC components, or any other vibrating
surface.
Mount the enclosure at least 12
feet (3.7 m) away from devices that
can generate Radio Frequency
Interference (RFI), such as Electro-
pneumatic devices (EPs), relays,
and walkie-talkies.
Mount the enclosure at least 5 feet
(1.5 m) away from 100 kVa or
larger motors and variable
frequency drives (VFD).

Summary of content (6 pages)