Installation Instructions

Installation Instructions
Document No. 553-620
November 10, 2011
18” PX Series Enclosure Assembly
Item Number 553-620, Rev. CA
Page 1 of 2
Product Description
The 18” PX series enclosure (see Figure 1) is UL-
508 listed for indoor use Type 1. The 18” PX series
enclosure can:
provide a degree of protection to personnel
against incidental contact with the enclosed
Siemens Building Control devices.
provide a degree of protection for those
devices against falling dirt.
The 18” enclosure is factory-equipped with the
following:
Factory-installed 16” by 12” perforated panel
DIN rail and wire tie bar kit
Pull-box type door, non-locking
The 18” PX series enclosure when installed per this
instruction is certified to comply with IBC 2009 and
CBC 2010 and may be used with following List of
Equipment / Components with OSHPD Special
Seismic Certification Preapproval (OSP)
OSP-217-10 and OSP-218-10
Product Numbers
PXA-ENC18 18” PX Series Enclosure Assembly
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedure as specified.
Required Tools and Materials
Adjustable wrench or pliers
Electric drill
Punch
Hammer
Level
Marker
Screwdrivers, small and medium Phillips
Tape measure
Tie-wraps
Wire stripper/side cutters
Four corrosion resistant 1/4” - 20 Bolts, flat
washers and nuts
To mount on concrete or masonry:
Hammer drill
1/2 inch carbide masonry bit
Four 1/4-20 corrosion resistant wall anchors
Prerequisites
CAUTION:
NEVER mount the enclosure on ductwork or
HVAC equipment.
Enclosure must be mounted at least 12 feet
(3.65 m) away from large motors and radio
equipment.
CAUTION:
Anchorage is not preapproved for Seismic
Certification and must be approved by the
Inspector of Record before installation.
Seismic Certification Preapproval requires:
Installed Equipment is listed in OSP.
Enclosures are non-isolated wall mounted
using four 1/4” minimum diameter bolts.
Total installed weight of enclosure,
installed equipment and wiring not to
exceed 50 lbs. Center of gravity for DIN
mounted equipment is at center of
enclosure.
DIN Rail mounted on backplane using
three supplied screws each.
Listed equipment not capable of being
installed on DIN rails may be fastened to
the backplane with supplied screws
.
Expected Installation Time
30 minutes
Installation
NOTE: Follow all safety regulations and local codes
when installing this equipment.
1. Draw a level line 6 feet (1.8 m) above the floor
on the wall or surface where the enclosure will
be mounted.