User Manual

Appendix:
Insight System Messages
280
---------------------------------------------------------------
Invalid Configuration
The telephony software has detected an invalid configura-
tion.
Cause:
- The partner, which is coupled by a modem, has no
telephone number.
Drop a Connection During Startup
A connection was dropped by the user.
Cause:
- The [STOP] key was pressed in the "Make a
Connection" window.
No Answer from Direct Partner
The directly coupled partner does not answer.
Causes:
- The connection to the DCS is broken.
- The DCS is in DILO.
- The DCS is switched off.
Transparent Connection
The directly coupled partner has not communicated; a
transparent connection was made.
Cause:
- See under "No Answer from Direct Partner."
End of Transparent Connection
The DCS has made a communication during the
transparent connection. There is now a normal connection.
Causes:
- The connection to the DCS was made.
- The DCS was booted.
Communication Port cannot be Initialised
The communication software cannot access to the port.
Causes:
- The port does not exist.
- The port is being used by another program.
- The computer no longer has enough memory capacity.
DCS Does Not Answer
BOO,D cannot be sent.
Communication Protocol Switched Off
Only a simple ASCII operation is possible.
Causes:
- Someone has executed BOO,D.
- A telephone communication is carried out manually.
---------------------------------------------------------------
CM2B8523E UNIGYR VISONIK Insight March 1995