User Manual
Appendix:
Insight System Messages
278
---------------------------------------------------------------
Modem Signal (CTS) Missing
The CTS signal is missing.
Causes:
- No modem
- Defective modem
- Modem not switched on.
- Wrong cable for link to the modem.
Partner Modem doesn't Answer
The partner station does not respond, or the dialling did
not function.
Causes:
- The partner modem is not configured correctly. (Auto-
Answer is not switched on.)
- The partner modem and/or the partner is not switched
on.
- The maximum wait time 'wc' was configured too short
in DSEQ; the wait time elapses before the partner re-
sponds. (The default is 45 seconds.)
- A wrong telephone number has been programmed.
- The dialled number is disabled on the local modem
(DIAL LOCKED)
No Valid Identification Received
The partner has not sent a valid configuration.
Causes:
- The partner is not a VISONIK System.
- Configuration error
- The connection is improper, preventing communication
(e.g. differing baud rates).
Invalid Address (configuration error)
The address which the partner sends does not correspond
to his own SS number (MUS).
Causes:
- Incorrect configuration of the communication. (MUS in
UVI.PRF and 'mu' in DSEQ of the partner
configuration.)
- The DCS is incorrectly configured.
Invalid Sender (configuration error)
The sender sent by the partner does not correspond to the
expected value (SS number of the partner).
Causes:
- Incorrect configuration of the communication. (SS
number in partner configuration)
- The partner entry is missing.
---------------------------------------------------------------
CM2B8523E UNIGYR VISONIK Insight March 1995