Appendix:
Communication Configuration 251
---------------------------------------------------------------
Name Enter any name, e.g. "Production"
Tel. No. Enter the partner's telephone number. The character ":" is
the waiting time.
Example: 0:041 34 35 36
SS No. Decimal SS number (in-house system number) as defined
in S,PROJ, e.g.:
"0" for System 0 (octal 300)
"130" for System 202 (octal)
If you are working in a network, "Insight" must have a
"SYS.INI" file with entries relating to the connected com-
puter. You will find further information in the file "Read
me."
Port Port used, e.g. COM3
Max. wait time Elapsed time until a modem connection break, if this is not
used (i.e., if no data exchange is taking place).
A warning appears after this elapsed time. If it is not
acknowledged, the connection is broken. Otherwise, the
wait time is reset.
Default wait time: 3 minutes. (0 means no monitoring.)
Max. connection time Maximum duration of a modem connection. When this
time has elapsed, a warning appears. If it is not acknowl-
edged, the connection is broken 30 seconds later. Other-
wise, the maximum connection time is reset.
Default time: 60 minutes. (0 means no monitoring.)
DSEQ Entry of partner-specific data, for example the decimal
number of the connection substation involved (also see
the Server Handbook, "Point Types and Parameters):
2: ;mu=168.
[OK]
The DCS can make a call via a modem-connected
"Insight," and transmit alarm messages (no pictures,
reports, etc.).
These alarms go to the "Messages" window.
To allow "Insight" to receive calls from the DCS, the fol-
lowing points must be observed:
- The modem must be configured such that "Auto an-
swer" is switched on.
For example, "ATSO=2" must be present in the DSEQ
of the appropriate port.
- The parameter MUS must be entered in the file
"UVI.PRF" (enter the SS number of "Insight"). The
default "0" is not permitted for incoming calls.
---------------------------------------------------------------
CM2B8523E UNIGYR VISONIK Insight March 1995