User Manual

A
Alarm Operation 143
---------------------------------------------------------------
9.1 Alarm updating
---------------------------------------------------------------
The function "Alarm Operation" only takes into account the
points which have been configured appropriately in the
DCS:
o The point must have a user address (parameter ADR)
o The parameter STZk must be set to "Alarm."
For purposes of simplification, such points are henceforth
often referred to as "Alarm points."
When the "Alarm Operation" function is started, the "Alarm
Operation" window appears empty.
Even later, changes in the alarm statuses of alarm points
are not automatically updated in the "Alarm Operation"
window.
"UNIGYR-VISONIK Insight" must continually be com-
manded to fetch the updated alarm data corresponding to
the currently set option (see title bar of window) from the
DCS:
IMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM M;
: :
"Alarm Operation" window
: :
Select "Command"
: :
Select "Update"
: :
HMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM M<
or
IMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM M;
: :
"Alarm Operation" window
: :
Select "Command"
: :
Choose "Select"
: :
HMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM M<
Now change the selection criteria as required, then
[OK]
The "Alarm Operation" window now contains the informa-
tion conforming to the currently set option and sort criteria.
The new incoming point information is sorted continuously
according to the selected sort criteria. For this reason, the
alarm list is set up anew several times.
---------------------------------------------------------------
CM2B8523E UNIGYR VISONIK Insight March 1995