Installation Instructions
Table Of Contents
- Figure 1. MS/TP Point Pickup Module.
- Product Description
- Product Numbers
- Caution Notations
- Expected Installation Time
- Prerequisites
- Installation
- Figure 2. Back plate knockout holes.
- Figure 3. Removing the cover
- Figure 4. Removing the PCB.
- Figure 7. Routing I/O wiring.
- Figure 8. Power Wiring.
- Figure 9. FLN 2 wire network interface.
- Figure 10. FLN 3-wire interface.
- Figure 11. Wiring I/O to terminals.
- Figure 12. 6 Point Digital controller board.
- Figure 13. 6 Point Analog controller board
- (PPM-2U3322.BPF and PPM-2U3322.BPR)
- (PPM-3U63.BPR, for China only)
- Figure 14. 12 Point Combination controller board.
- Table 1. DIP Switch Settings for Baud Rate.
- Figure 15. Installing front cover to back plate.
- Figure 16. MSTP PPM Dimensions.
- I/O Configuration Diagrams
- Figure 17. AI/DI wiring for 6 point digital.
- Figure 18. DO wiring for wiring for 6 point digital.
- Figure 19. Analog input wiring.
- Figure 20. Universal input wiring.
- Figure 21. Analog output wiring.
Document No. 550-992
Installation Instructions
August 20, 2014
Page 4 of 6 Siemens Industry, Inc.
Figure 11. Wiring I/O to terminals.
Figure 12. 6 Point Digital controller board.
Figure 13. 6 Point Analog controller board
(PPM-2U3322.BPF and PPM-2U3322.BPR)
(PPM-3U63.BPR, for China only)
Figure 14. 12 Point Combination controller board.
9. Set the address using DIP Switches 1 through 8
(Binary 0 to 255)
Example 1: Switch 7 and 8 ON = Address 3.
Example 2: Switch 5 and 8 ON = Address 9.
10. Note the device’s MAC and network number, as
this may be required for startup.
11. Set the device’s communication speed (baud
rate) by using DIP Switches 9 and 10, following
the settings in Table 1.
Table 1. DIP Switch Settings for Baud Rate.
Baud Rate Switch 9 Switch 10
9600
OFF
OFF
19200
OFF
ON
38400
ON
OFF
76800
ON
ON
12. Restore power.
NOTE: The 6 point digital (PPM-1U32.BPR)
has a HOA switch for commissioning.