Installation Instructions

Document No. 550-992
Installation Instructions
August 20, 2014
Page 4 of 6 Siemens Industry, Inc.
Figure 11. Wiring I/O to terminals.
Figure 12. 6 Point Digital controller board.
Figure 13. 6 Point Analog controller board
(PPM-2U3322.BPF and PPM-2U3322.BPR)
(PPM-3U63.BPR, for China only)
Figure 14. 12 Point Combination controller board.
9. Set the address using DIP Switches 1 through 8
(Binary 0 to 255)
Example 1: Switch 7 and 8 ON = Address 3.
Example 2: Switch 5 and 8 ON = Address 9.
10. Note the device’s MAC and network number, as
this may be required for startup.
11. Set the device’s communication speed (baud
rate) by using DIP Switches 9 and 10, following
the settings in Table 1.
Table 1. DIP Switch Settings for Baud Rate.
Baud Rate Switch 9 Switch 10
9600
OFF
OFF
19200
OFF
ON
38400
ON
OFF
76800
ON
ON
12. Restore power.
NOTE: The 6 point digital (PPM-1U32.BPR)
has a HOA switch for commissioning.