Installation Instructions
Table Of Contents
- Figure 1. MS/TP Point Pickup Module.
- Product Description
- Product Numbers
- Caution Notations
- Expected Installation Time
- Prerequisites
- Installation
- Figure 2. Back plate knockout holes.
- Figure 3. Removing the cover
- Figure 4. Removing the PCB.
- Figure 7. Routing I/O wiring.
- Figure 8. Power Wiring.
- Figure 9. FLN 2 wire network interface.
- Figure 10. FLN 3-wire interface.
- Figure 11. Wiring I/O to terminals.
- Figure 12. 6 Point Digital controller board.
- Figure 13. 6 Point Analog controller board
- (PPM-2U3322.BPF and PPM-2U3322.BPR)
- (PPM-3U63.BPR, for China only)
- Figure 14. 12 Point Combination controller board.
- Table 1. DIP Switch Settings for Baud Rate.
- Figure 15. Installing front cover to back plate.
- Figure 16. MSTP PPM Dimensions.
- I/O Configuration Diagrams
- Figure 17. AI/DI wiring for 6 point digital.
- Figure 18. DO wiring for wiring for 6 point digital.
- Figure 19. Analog input wiring.
- Figure 20. Universal input wiring.
- Figure 21. Analog output wiring.
Installation Instructions
Document No. 550-992
August 20, 2014
MS/TP Point Pickup Modules
Rev. BA Page 1 of 6
Figure 1. MS/TP Point Pickup Module.
Product Description
The Siemens MS/TP Point Pickup Module (PPM) is
a BACnet Application Specific Controller that
communicates on a BACnet MS/TP network. The
PPM extends the host BACnet Building Controllers
control program for local or distributed point
expansion.
The MTSP Point Pickup Module Family includes 6
point analog, 6 point digital and 12 point combination
module options with a wide range of sensor type
support.
Product Numbers
Digital PPM-1U32.BPF (1 Universal Input, 3DI,
2DO, fixed terminal blocks)
Digital PPM-1U32.BPR (1 Universal Input, 3DI,
2DO, removable terminal blocks and manual
override switches for commissioning checkout)
Analog PPM-2U22.BPF (2 Universal Input, 2AO,
2AI, fixed terminal blocks)
Analog PPM-2U22.BPR (2 Universal Input, 2AO,
2AI, removable terminal blocks)
Combination PPM-2U3322.BPF (2 Universal Input,
3DI, 3DO, 2AO, 2AI, fixed terminal blocks)
Combination PPM-2U3322.BPR (2 Universal Input,
3DI, 3DO, 2AO, 2AI, removable terminal blocks)
Combination PPM-3U63.BPR (for China only)
(3 Universal Input, 6DI, 3DO, removable terminal
blocks)
Caution Notations
CAUTION:
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.
Required Tools
• Small flat-blade screwdriver 0.11” (3-mm)
• Small Phillips screwdriver 0.15" (4-mm)
• Cordless drill/driver set
• Pliers
• Permanent marker or label maker
Expected Installation Time
Average installation time is 15 minutes. This will vary
depending on the device and IO counts.
Prerequisites
• Wiring conforms to NEC and local codes
and regulations. For more information, refer
to the Wiring Guidelines manual (125-3002).
• 24 Vac Class 2 power source available.
• Supply power to the device is OFF.
• Any application specific hardware or devices
are installed.