Data Sheet for Product
Table Of Contents
BACnet Protocol Implementation Conformance Statement
9
Siemens Technical Specification Sheet 149-220
2014-08-12
BACnet Standard Application Services Support
Name
ReadProperty Execute
ReadPropertyMultiple Execute
WriteProperty Execute
UnconfirmedCOVNotification Initiate
DeviceCommunicationContro Execute
I-Am Initiate
I-Have Initiate
Who-Has Execute
Who-Is Execute
Data Link Layer Options
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________
• MS/TP master (Clause 9), baud rate(s): 9600 bps, 19200 bps, 38400 bps, 76800 bps
• MS/TP slave (Clause 9), baud rate(s): ____________
Point-To-Point, EIA 232 (Clause 10), baud rate(s): _________________
Point-To-Point, modem, (Clause 10), baud rate(s): _________________
LonTalk, (Clause 11), medium: _________________________________
Other: _____________________________________________________
Segmentation Capability
Able to transmit segmented messages Window Size: 32
Able to receive segmented messages Window Size: 32
Device Address Binding
Is Static Device Binding supported? No