Data Sheet for Product

BACnet Protocol Implementation Conformance Statement
26
Siemens Technical Specification Sheet 149-220
2014-08-12
Analog Input Object Type
Analog Input Object Type
Property_Identifier Supported Access Notes
Object_Identifier Yes
Object_Name Yes
Object_Type Yes
Present_Value Yes W
Description No
Device_Type No
Status_Flags Yes
Event_State Yes
Reliability Yes
Out_Of_Service Yes W
Update_Interval No
Units Yes W
Min_Pres_Value No
Max_Pres_Value No
Resolution No
COV_Increment Yes W
Time_Delay No
Notification Class No
High_Limit No
Low_Limit No
Deadband No
Limit_Enable No
Event_Enable No
Acked_Transitions No
Notify_Type No
Event_Time_Stamps No
Profile_Name No
Analog Output Object Type
Property_Identifier Supported Access Notes
Object_Identifier Yes
Object_Name Yes
Object_Type Yes
Present_Value Yes W
Description No
Device_Type No