Data Sheet for Product

Digital Point Pickup Module
Specifications
Power
Requirements
Operating Range
Power
Consumption
Input power range of
19.2 Vac to 28.8 Vac
(50 or 60 Hz)
4 VA
Inputs
Analog
Digital
1 Configurable 10K
Type II NTC Thermistor
3 Fixed dry contact or LPACI and
1 Configurable dry contact or
LPACI
Outputs
Digital
Two Form A NO (Normally
Open) Relays with a shared
common.
24 to 250 Vac, 3A resistive,
2A General Purpose, 3(2)
Temperature
Monitoring
Accuracy
±0.25°F
over a range of 55°F to 95°F
(13°C to 35°C)
NOTE: PPMs have a hard coded range, if the value
goes below 20°F (-6.7°C) or above 120°F (48.9°C), the
point will display FAILED.
Dimensions
4.5 in x 4.5 x 1.4 in
(114.3 mm x 114.4 mm x 34.5 mm)
Weight
0.5 lb
Communications
Remote
Local
4800 to 115200 bps FLN Trunk
None
Storage
Temperature
Operating
Temperature
Range
-40°F to 158°F (-40°C to 70°C)
32°F to 122°F (0°C to 50°C)
5% to 95% rh (non-condensing)
Agency Listings
UL Listing
cUL Listed
FCC Compliance
UL 916, PAZX, PAZX7
Canadian Standards C22.2 No.
205
Part 15 Class B
CISPR 22 Class B
RCM conformity
EU conformity (CE)
Environmental
Compliance
Meets EU RoHS Requirements
WEEE Compliant
OSHPD
Certification
Product meets OSHPD Special
Seismic Preapproval certification
(OSH-0217-10) under California
Building Code 2010 (CBC2010)
and International Building Code
2009 (IBC2009) when installed
within Siemens enclosure part
numbers; PXA-ENC18, PXA-
ENC19 or PXA-ENC34.
Product Ordering Information
Description Product Part
Numbers
Digital Point Pickup Module
(Asia Pacific Version with Fixed
Terminal Blocks)
PPM-1U32.PPF
Point Pickup Module DIN Kit
(Kit includes 10 mounting brackets
and 10 screws, capable of
mounting up to 5 PPMs)
PPM-DINKIT
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners.
© 2013 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
Your feedback is important to us. If you have
comments about this document, please send them to
SBT_technical.editor@siemens.com
Document No. 149-816
Printed in the USA
Page 2 of 2