Installation Instructions

Installations Instructions
Document No. 129-224
September 29, 2009
ASC9.4U Dual Auxiliary Switch
Item Number 129-224, Rev. 300 Page 1
Product Description
This package contains a dual auxiliary switch with 3-
foot long cabling, and a black NEC Class I compliant
compartment cover for use on the SQX8... three-
position valve actuator.
Product Number
ASC9.4U
Installation Conventions
Warning
Personal injury/loss of life may
occur if a procedure is not
performed as specified.
Caution
Equipment damage, or loss of
data may occur if the user
does not follow procedure as
specified.
Required Tools
1/8” and 1/4” flat blade screwdrivers
Hammer
Expected Installation Time
45 minutes
Prerequisites
Warning:
Disconnect power supply to the
actuator before beginning to install the
switch
Installation
1. Use a 1/4” flat blade screwdriver to remove the
actuator cover. Discard the cover.
2. Remove the upper conduit opening knock-out.
Refer to Figure 1.
;
EAO431R1
UPPER
CONDUIT
KNOCK-OUT
Figure 1
3. Attach a threaded connector onto 2 feet (60 cm) or
less of flexible metal conduit.
4. Remove the switch from its packaging.
5. Slip the conduit connector nut over the wires.
Refer to Figure 2.
EA0432R1
Figure 2. Placing the Conduit Connector Nut.
6. Slip the wires through the actuator housing conduit
knock-out keeping the conduit connector nut
inside the actuator.
7. Feed the wires through the flexible metal conduit.
Refer to Figure 3.
;
;
EAO434R2
Figure 3. Feeding wires through Conduit.
8. Attach the threaded connector to the actuator
housing with the connector nut. Refer to Figure 4.
EA0433R2
;
;
Figure 4. Fastening the Connector to the Actuator.