Installation, Continued
11. Make pneumatic piping connections to the
actuator and relay. The "S" Port is the air supply
port. The "M" Port goes to the connector on the
actuator. The "T" Port is the signal from the
controller. See Figure 3.
Figure 3. Mounting Relay Ports.
12. Place the calibration label on the cover as
shown in Figure 3. Mark for reference. (Optional)
Attach the relay cover if you are not calibrating
immediately.
13. Calibrate the relay by following the instructions
included with the positioning relay.
The installation is now complete.