User Manual

Technical data
6
17 |
29
Siemens Industry, Inc.
A6V10958126_en
--
_a
Building Technologies
2017
06
-
30
6 Technical data
Power supply*
Operating voltage KNX/PL-Link DC 21...30V
Max power consumption 7...10 mA
Interfaces
Type of port between room automation
station and room operator unit
KNX/ PLLink
Baud rate 9.6 kbps
Protocol KNX PL-LINK
Standard KNX plug Wire diameter 0.8 mm, max. 1.0 mm
Cable type 2-core twisted pair, stranded, solid
Single cable length (from room automation
station to room operator unit)
<1000 m
Section 0,5…1,5 m
Bus line polarity PL+,PL-
Bus terminating resister not required
Sensor data
Temperature Sensor Measuring element NTC resistance sensor
Measuring range 0..50°C
Measuring accuracy (5...30°C) ±0.8°C
Measuring accuracy (25°C) ±0.5°C
Humidity Sensor Measuring range 10%...95% rh
Accuracy (rh 20%...80%) ±4% at 25°C
Accuracy (rh 0%...20%, 80%...95%) ±6% at 25°C
Ambient conditions and protection classification
Housing Protection
Protection standard as per EN 60529
IP30
IP33 for surface part
Insulation protection class Class III
Climatic ambient conditions
Normal operation
Transport
Environmental Conditions: Class 3K5
Temperature 0...50°C (0... 122 F)
Air humidity <85% rh
Environmental Conditions: Class 2K3
Temperature -25...70°C (-4... 158 F)
Air humidity <95% rh
Mechanical ambient conditions
Normal operation
Transport
Class 3M2
Class 2M2