Data Sheet for Product

2
Siemens
A6V11417931_en--_b
Smart Infrastructure
2020-07-08
Features
The controller is configurable and is delivered with a pre-loaded, pre-engineered and fully
tested application developed for heat recovery ventilation applications.
Inputs and outputs (I/Os)
The controller’s I/O mix is dedicated for heat recovery ventilation (HRV).
10 inputs
4 analog inputs for temperature sensor (B1…B4)
2 digital inputs for galvanically isolated AC or DC 24 V (D1, D2)
1 multi-functional input for digital potential-free contacts and temperature sensors (X8)
2 multi-functional inputs for 0…10 V, 4…20 mA, digital, pulse, mutli-state (X1…X2)
1 multi-functional input for 0…10 V, 4…20 mA, digital, pulse, multi-state and temperature
sensors (X3)
8 outputs
4 analog outputs for DC 0…10 V (A1…A4)
3 digital relay outputs (3 NO contacts, SPST) (Q1…Q3)
1 triac output AC 24…230 V (Y1)
Communication
The S300 control platform is IP-ready and comes with open communication protocols for
flexible integration.
BACnet communication over RJ45 Ethernet IP to connect to router for direct Internet
connectivity, or to connect to WLAN gateway for communication using a mobile device
USB connection for firmware up-/download with USB stick, or temporary WLAN stick for
communication using a mobile device during commissioning using ABT Go
1 Modbus RTU master over RS485 for integration in building automation and control
2 Modbus RTU slaves over RS485 to communicate with peripherals
KNX PL-Link bus to communicate with room units and sensors
I/O extensions with pressure sensors
The controller’s I/Os can be extended with I/O extensions and sensors for bigger plants via
Modbus master port.
POS9 (PCB variant)
2 air pressure sensors on PCB to measure absolute and differential pressure
1 Modbus RTU RS485 to communicate with the controller
2 multi-functional inputs: Digital, temperature sensors (X21) and digital 0…10 V (X22)
2 multi-functional outputs: DC 0…10 V and PWM (A21) and relay output (Q21)
QBM97 (variant with housing)
2 air pressure sensors 05007000 Pa to measure absolute and differential pressure
1 Modbus RTU RS485 to communicate with the controller
2 multi-functional inputs for DC 0…10 V, Ni1000, Pt1000, NTC10k, LG-Ni1000 (NTC10k
configured only for AI1 and 0-10 V configured only for AI2)
2 multi-functional outputs for DC 0…10 V (AO1/2)
Modbus Fan
Up to 2 Modbus EBM Papst fans. For additional information please refer to the
manufacturer’s web site
https://www.ebmpapst.com