Data Sheet for Product
15
Siemens
A6V11417931_en--_b
Smart Infrastructure
2020-07-08
Onboard Triac output
Endurance
Max. 4’000’000 cycles for 1 A resistive load
Min. cycle time (configurable) of PWM signal
≥ 1 s / 1 Hz
Max. external supply line fusing
2.5 A circuit breaker
Digital (binary) / analog output triac VAC
signal On/Off,
signal PWM (constant period))
Analog outputs
A1 (T2)
A2, A3, A4 (T18)
Analog output
Configurable voltage range
0...5 V or 0...10 V
Ripple
< 50 mVpp
Accuracy at 0 V
Accuracy at 5 V
Accuracy at 10 V
80 mV
100 mV
130 mV
Output current
Max. 1 mA