Data Sheet for Product

8 / 20
Siemens Climatix Extension Modules ECV2 CB1N3944en
Smart Infrastructure 2021-02-16
These data are acquired under operating temperature of 25 °C.
Analog inputs (X9…X10)
Ni1000
Sensor current Max. 1.4 mA
Resolution 0.3 K
Accuracy in the range -50…150 °C 0.7 K
Pt1000
Sensor current Max. 1.8 mA
Resolution 0.3 K
Accuracy in the range -40…120 °C 1.0 K
NTC 10k (B
25/85
= 3977 K)
Sensor current Max. 500 μA
Note