Data Sheet for Product
17 / 20
Siemens Climatix Extension Modules ECV2 CB1N3944en
Smart Infrastructure 2021-02-16
internal super capacitor has still power, the internal application starts again and can
control the outputs (therefore BSP LED green).
Firmware of POL98X.00/XXX features different diagnostic functions such as
disconnection detection, under voltage detection or shorted coil. The function
"disconnection detection" is active only during valve / motor positioning, not during
hold on.
DIP switch is equipped with the extension module to communicate with the
controller. Switch 1, 2, 3, 4, and 5 are configurable to set the slave address, while
switch 6 acts as peripheral bus termination. When extension module works as the
termination in the network, switch 6 needs to be set as ON.
The order of bits for the switch is from 5 to 1, 5 is the lowest bit, while 1 is the
highest bit. The following table shows the logic of slave address:
Switch 1
2
4
Switch 2
2
3
Switch 3
2
2
Switch 4
2
1
Switch 5
2
0
By combining switches 1, 2, 3, 4 or 5, maximum 31 slave addresses can be
configured. The configuration formula is as below: 2
4
+2
3
+2
2
+2
1
+2
0
=31.Below are
some configuration examples:
DIP Switch configuration of extension module
No. Schematics No. Schematics No. Switch 5 No. Schematics
1 9 17 25
2 10 18 26
3 11 19 27
4 12 20 28