Functions
LEDs "BSP" and "BUS" for diagnostics
LED Color Flashing frequency Meaning/Mode
BSP Red/Green 1 s red / 1 s green BSP upgrade mode
Orange Flashing at 1 Hz BSP upgrade failed, bad image
Orange/Green 1 s orange / 1 s green BSP upgrade partial done, wait for continue
Green Steady "on" BSP operating and communication with controller working
Orange Steady "on" BSP operating but no communication with controller
Red Flashing at 2 Hz BSP error (Software error)
Red Steady "on" Hardware fault
Red/Orange 500 ms / 1000 ms Emergency OS is operating, execute BSP upgrade again
BUS Green Steady "on" ● Communication active
Red Steady "on" ● BACnet server down
● No communication (DCC is set to disable)
● Ethernet link is down
Orange Steady "on" ● Initializing - no communication yet via IP
● Restricted communication (DCC is set to disable-initiation)
If both LEDs stay dark:Power supply is outside the allowed range!
Ordering
Type Stock number Designation
POL908.00/STD S55390-C106-A100 BACnet IP communication module
Delivery
Included is:
Phoenix Type Designation
ZEC 1,0/10-LPV-3,5 GY35AUC2CI1 Board-to-board COMM interface plug
Devices are from PHOENIX CONTACT, www.phoenixcontact.com.
Product documentation
Document ID Title Topic
Q3900en Climatix range Climatix product range
M3910 Mounting instruction Climatix Mounting and installation
P3939en PICS BACnet protocol implementation conformance
statement