Data Sheet for Product
9 / 18
Siemens Climatix range CB1Q3900en_02
Building Technologies 30.11.2009
Addressing the extension modules
The extension modules are equipped with DIP switches for communication with the
controller. Switches 1, 2, 3, 4, and 5 are configurable to set the slave address,
while switch 6 acts as peripheral bus termination. When the extension module op-
erates as the termination in the network, switch 6 must be set to ON.
By combining switches 1, 2, 3, 4 or 5, a maximum of 31 slave addresses can be
configured. Below are some configuration examples:
DIP switch configuration of extension module
Slave address
(controller)
Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Schematics
1 Off Off Off Off On
2 Off Off Off On Off
3 Off Off Off On On
4 Off Off On Off Off
5 Off Off On Off On
6 Off Off On On Off
7 Off Off On On On
8 Off On Off Off Off
DIP switches