Data Sheet for Product

16 / 18
Siemens Climatix range CB1Q3900en_02
Building Technologies 30.11.2009
Power supply AC24V DC24V
mA W
Required nr. of POL635.00
1800 22 Climatix 635 - 21 I/Os
Required nr. of POL636.00
1800 22 Climatix 636 - 21 I/Os
Required nr. of POL638.00
1800 22 Climatix 638 - 21 I/Os
Required nr. of POL638.70
1800 22 Climatix 638 - 21 I/Os - with inbuilt HMI
Required nr. of POL687.00
1800 22 Climatix 687 - 27 I/Os
Required nr. of POL687.70
1 1800 22 Climatix 687 - 27 I/Os - with inbuilt HMI
Required nr. of POL985.00
850 11 Extension 26 I/Os
Required nr. of POL965.00
4 750 10 Extension 15 I/Os
Required nr. of POL955.00
750 10 Extension 14 I/Os
Required nr. of POL94E.00
900 12 Extension 6 I/Os - ECV
Required nr. of POL94U.00
4 900 12 Extension 6 I/Os - ECV with inbuilt UPS
Required nr. of POL945.00
2 260 3 Extension 8 I/Os
Required nr. of POL925.00
150 1.5 Extension 6 I/Os
Required nr. of POL902.00
Communication card Modbus RS-485
Required nr. of POL904.00
Communication card BACnet MSTP
Required nr. of POL906.00
Communication card LON
Required nr. of POL908.00
Communication card BACnet IP
Required nr. of POL909.00
Communication card advanced Web
Required nr. of POL895.50
Human Machine Interface
Power supply AC24V DC24V
Sum of currents 8.92 4.83
Total apparent power [VA] 214.08 116.00
Max. 96 VA for both AC 25 V or DC 24 V power supplies
Example with two
DC 24 V power supplies: