Data Sheet for Product

6
Building Technologies
CB1Q3936en
Building Technologies 2018-02-23
Notes
Securit
y: National safety regulations
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage
Observe national provisions and comply with the appropriate safety regulations.
Engineering: concept
The M-Bus module is attached to the controller with a board-to-board connector
The connection to the M-Bus is made via the T1 port
For service, use the M-Bus service button
Commissioning
Meter setting
Prior to connecting the M-Bus module, the following meter settings must be made:
Primary address from 1 to 250 (physical address)
Baud rate 300 / 600 / 1200 / 2400 / 4800 / 9600 baud
Enabling the required data, storage no. = 0, tariff = 0
Energy in kWh
Volume in m
3
Power in W
Flow rate in l/h
Flow temperature in °C
Return temperature in °C
Enabling the required data, storage no. = 1, tariff = 0
Date of set day: Day, month, (year)
Energy in kWh on the set day
Volume in m
3
on the set day