Data Sheet for Product
6
Building Technologies
CB1Q3936en
Building Technologies 2018-02-23
Notes
Securit
y: National safety regulations
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage
● Observe national provisions and comply with the appropriate safety regulations.
Engineering: concept
● The M-Bus module is attached to the controller with a board-to-board connector
● The connection to the M-Bus is made via the T1 port
● For service, use the M-Bus service button
Commissioning
Meter setting
Prior to connecting the M-Bus module, the following meter settings must be made:
● Primary address from 1 to 250 (physical address)
● Baud rate 300 / 600 / 1200 / 2400 / 4800 / 9600 baud
● Enabling the required data, storage no. = 0, tariff = 0
– Energy in kWh
– Volume in m
3
– Power in W
– Flow rate in l/h
– Flow temperature in °C
– Return temperature in °C
● Enabling the required data, storage no. = 1, tariff = 0
– Date of set day: Day, month, (year)
– Energy in kWh on the set day
– Volume in m
3
on the set day
Disposa
l
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.