Data Sheet for Product

5
Building Technologies
CB1Q3936en
Building Technologies 2018-02-23
Functions
LEDs "BSP" and "BUS" for diagnostics
LED Color Flashing frequency Meaning/Mode
BSP Red/Green 1 s red / 1 s green BSP upgrade mode
Green Steady "on" BSP running and communication with controller
Orange Steady "on" BSP running, but no communication with controller
Red Flashing at 2 Hz BSP error (Software error)
Red Steady "on" Hardware fault
BUS Green Steady "on" M-bus running and communication ok
Red Steady "on" No M-Bus device is running
Orange Steady "on" At least one M-Bus device is not running
If both LEDs stay dark: Power supply is outside the allowed range!
Ordering
Type Stock number Designation
POL907.00/STD S55390-C108-A100 Climatix M-Bus module
Delivery/Included:
Phoenix Type Designation
ZEC 1,0/10-LPV-3,5 GY35AUC2CI1 Board-to-board COMM interface plug
1 x 2 pos - FKCT 2,5 /2-ST Terminal plugs
Devices are from PHOENIX CONTACT, www.phoenixcontact.com.
Product documentation
Document ID Title Topic
Q3900en Climatix range Climatix product range
M3910 Mounting instruction Climatix Mounting and installation
BSP