Data Sheet for Product
4
Siemens
CB1Q3931en
Building Technologies 2017-06-12
Standards, directives and approvals
Product standard EN 60730-1
Automatic electronic controls for household and similar use
Electromagnetic compatibility For residential, commercial, and industrial environments
EU conformity (CE) CB1T3930xx
RCM conformity CB1T3909en_C1
Listings UL916, UL873 http://database.ul.com/
CSA Class 4812 http://www.csagroup.org
EAC Eurasian conformity
Environmental compatibility The product environmental declaration (CB1E3950_01) contains data
on environmentally compatible product design and assessments
(RoHS compliance, materials composition, packaging, environmental
benefit, disposal).
Functions
LON service pin button
The LON service pin button is used for LON addressing.
LEDs "BSP" and "BUS" for diagnostics
LED Color Flashing frequency Meaning/Mode
BSP Red/Green 1 s red / 1 s green BSP upgrade mode
Green Steady "on" BSP operating and communication with controller working
Orange Steady "on" BSP operating, but no communication with controller or upgrade mode
active
Red Flashing at 2 Hz BSP error (Software error)
Red Steady "on" Hardware fault
BUS Green Steady "on" ● Ready for communication (all parameters loaded, Neuron configured)
● Does not indicate communication with other devices
Red Steady "on" ● No communication to Neuron
● Internal error, could be solved by downloading a new LON
application
Orange Steady "on" ● Startup
Orange Flashing ● Communication not possible to the Neuron
● The Neuron must be configured and set online over the LON Tool
If both LEDs stay dark: Power supply is outside the allowed range!
BSP