s 3 900 ClimatixTM Climatix range POL68X.XX/XXX, POL63X.00/XXX, POL985.00/XXX, POL965.00/XXX POL955.00/XXX POL94U.00/XXX, POL94E.00/XXX POL945.00/XXX, POL925.00/XXX POL902.00/XXX POL904.00/XXX, POL906.00/XXX POL907.00/XXX, POL908.00/XXX POL909.00/XXX The products of the Climatix range are designed for use in ventilation, air conditioning, refrigeration and district heating plants.
Communication concept POL68X Communication concept POL63X 2 / 18 Siemens Building Technologies Climatix range CB1Q3900en_02 30.11.
Climatix 600 range overview Climatix 6XX products are designed for use in ventilation, air conditioning, refrigeration and district heating plants and provide a broad range of control and monitoring functions. The product range is of modular design and primarily comprises controllers (versions with or without HMI) and different add-on I/O modules, including step motor and factory- or field-mounted communication modules.
Climatix 6XX - product range 2 2 Max Total 8 5 8 5 8 5 8 5 8 2 2 2 2 2 2 3 2 1 8 8 8 8 max 6 max 6 max 6 max 6 max 4 max 4 max 4 max 4 max 4 max 4 max 4 max 4 POL902 POL904 POL906 POL907 POL908 POL909 Communication modules Yes Yes Yes Yes Yes Yes ◄ 2 2 2 2 6 6 6 6 21 2 21 2 21 2 21 2 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 1 1 Yes Yes 1 1 Yes Yes Yes 1 1 Yes Yes Yes Yes Yes Yes Yes Yes Yes 1 1 1 1 1 1 1 2
Climatix product range Controllers and HMIs POL687.00/ POL687.70/ with HMI (refer to Data Sheet 3903) (refer to Data Sheet 3903) POL635.00/ POL636.00/ with HMI POL638.00/ with HMI (refer to Data Sheet 3230) (refer to Data Sheet 3230) (refer to Data Sheet 3230) Extension modules POL985.00/ POL965.00/ POL955.00 (3221) (3222) (3226) POL94U.00/ POL94E.00/ POL945.00/ POL925.00/ (3225) (3225) (3223) (3224) User interface POL895.00/ external HMI (3941) Communication modules POL902.
SW tools ACX93.00 SAPRO programming tool SCOPE commisioning tool Connecting the components Communication Board-tomodule Board-to- Extension board Controller with inbuilt HMI board module connector connector Configuration example Communication Controller with HMI Extension modules module 6 / 18 Siemens Building Technologies Climatix range CB1Q3900en_02 30.11.
Ordering data for accessories Peripheral bus Board-to-board Phoenix ZEC1,0/4-LPV-3,5 GY35AUC2CI1 Board-to-wire Phoenix ZEC1,0/4-ST-3,5 GY35AUC1R1,4 COMM interface Board-to-board Phoenix ZEC1,0/10-LPV-3,5 GY35AUC2CI1 Accessories for controllers Real time clock battery BR2032 PC service cable 150 cm SAPRO programming tool license Test and demo case POL 0B1.20/STD POL 0C2.40/STD ACX93.000 POL 0G6.87/STD POL 068.
Connecting the extension modules Cabling and grounding rules Specification for pheripheral bus cable and power supply: • If the total length of the pheripheral bus cable exceeds 3 m, shielded cables must be used (L1 + L2 + Lx = >3 m) • If the total length of the pheripheral bus cable is less than 3 m, shielded cables are not required (L1 + L2 + Lx = <3 m) • Each shield must be grounded at one side only • Maximum bus cable length is 30 m (L1 + L2 + Ln = <30 m) • To connect the bus cable to the modules, use
Addressing the extension modules DIP switches The extension modules are equipped with DIP switches for communication with the controller. Switches 1, 2, 3, 4, and 5 are configurable to set the slave address, while switch 6 acts as peripheral bus termination. When the extension module operates as the termination in the network, switch 6 must be set to ON. By combining switches 1, 2, 3, 4 or 5, a maximum of 31 slave addresses can be configured.
DIP switch configuration of extension module Slave address Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 9 Off On Off Off On 10 Off On Off On Off 11 Off On Off On On 12 Off On On Off Off 13 Off On On Off On 14 Off On On On Off 15 Off On On On On 16 On Off Off Off Off 17 On Off Off Off On 18 On Off Off On Off 19 On Off Off On On 20 On Off On Off Off 21 On Off On Off On 22 On Off On On Off 23 On Off On On On 24 On
DIP switch configuration of extension module Slave address Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 27 On On Off On On 28 On On On Off Off 29 On On On Off On 30 On On On On Off 31 On On On On On (controller) Note Schematics The same address of extension module must be set in the application program of the controller. Zero cannot be set as the slave address.
Power consumption table for controllers and modules Type POL635.00 Amount mA VA 1800 22 Climatix 636 / 21 I/Os POL636.00 1800 22 Climatix 636 / 21 I/Os POL638.00 1800 22 Climatix 638 / 21 I/Os POL638.00 1800 22 Climatix 638 / 21 I/Os with inbuilt HMI POL687.00 1800 22 Climatix 687 / 27 I/Os POL687.70 1800 22 Climatix 687 / 27 I/Os with inbuilt HMI POL685.00 850 11 Extension module 26 I/Os POL965.00 750 10 Extension module 15 I/Os POL955.
Pass-through current simulator Pass-through current calculator for Power Supply AC 24V or DC 24V Power supply type Required nr. of POL635.00 Required nr. of POL636.00 Required nr. of POL638.00 Required nr. of POL638.70 Required nr. of POL687.00 Required nr. of POL687.70 Required nr. of POL985.00 Required nr. of POL965.00 Required nr. of POL955.00 Required nr. of POL94E.00 Required nr. of POL94U.00 Required nr. of POL945.00 Required nr. of POL925.00 Required nr. of POL902.00 Required nr. of POL904.
Example with two AC 24 V power supplies: This example shows how to use one POL687.70 controller together with 2 POL965, 2 POL954 and 2 POL94U extension modules. This combination is not possible with only one AC 24 V power supply, since the total apparent power exceeds 96 VA (note that it could be done using DC 24 V). Power supply AC 24 V DC 24 V mA W Required nr. of POL635.00 1800 22 Climatix 635 - 21 I/Os Required nr. of POL636.00 1800 22 Climatix 636 - 21 I/Os Required nr. of POL638.
So we split the group into subgroup 1 and subgroup 2 Pass-through current calculator for each power supply mA Required nr. of POL635.00 1800 Pass-through current calculator for each power supply W mA W 22 Required nr. of POL635.00 1800 22 Required nr. of POL636.00 1800 22 Required nr. of POL636.00 1800 22 Required nr. of POL638.00 1800 22 Required nr. of POL638.00 1800 22 Required nr. of POL638.70 1800 22 Required nr. of POL638.70 1800 22 Required nr. of POL687.
Example with two DC 24 V power supplies: Power supply AC24V DC24V mA W Required nr. of POL635.00 1800 22 Climatix 635 - 21 I/Os Required nr. of POL636.00 1800 22 Climatix 636 - 21 I/Os Required nr. of POL638.00 1800 22 Climatix 638 - 21 I/Os Required nr. of POL638.
So we split the group into subgroup 1 and subgroup 2 Pass-through current calculator for each power supply mA Required nr. of POL635.00 1800 Required nr. of POL636.00 1800 Required nr. of POL638.00 1800 Pass-through current calculator for each power supply W mA W 22 Required nr. of POL635.00 1800 22 22 Required nr. of POL636.00 1800 22 22 Required nr. of POL638.00 1800 22 Required nr. of POL638.70 1800 22 Required nr. of POL638.70 1800 22 Required nr. of POL687.
/ 18 2009 Siemens Switzerland Ltd. Siemens Building Technologies Climatix range Subject to change CB1Q3900en_02 30.11.