Data Sheet for Product
6
Siemens CB1Q3903en
Smart Infrastructure 2020-04-08
WARNING
Note the following for installation:
● Do not mix SELV / PELV and mains power on the same terminal
●
Use external protection for inductive load
Triac outputs DO1, DO2 (T11)
Triac output values
Switching voltage AC 24…230 V (-20%, +10%)
Switching capacity Max. 500 mA / min. 30 mA
External fuse in the supply line Max. 2.0 A slow wire fuse or circuit breaker
Connecting solenoid valves to triac output
WARNING
Note the following for installation:
● Do not mix SELV / PELV and mains power on the same terminal
●
Use external protection for inductive load