Data Sheet for Product

17
Siemens CB1Q3903en
Smart Infrastructure 2020-04-08
Terminals
Connection terminals
Solid wire 0.5…2.5 mm²
Stranded wire (twisted and with ferrule) 0.5…1.5 mm²
Cable lengths In compliance with the load, local regulations and
installation documents
Cable types
Process bus Twisted pair; 0.5…1.5 mm2
(per KNX specification)
RS-485 interface 2-wire, twisted pair , shielded
Periphery bus 4-wire (2 wires as twisted pair), shielded
Conformity
Environmental conditions
Operation IEC 60721-3-3 class 3K5
Temperature -40...70 °C
Restriction LCD -2060 °C
Restriction process bus -25…70 °C
Restriction with 1 COM module -40…65 °C
Restriction with 2 COM modules -40…60 °C
Humidity <90% r.h. (non-condensing)
Air pressure Min. 700 hPa (corresponding to max. 3,000 m
above sea level)
Mechanical conditions IEC 60721-3-3 class 3M2
Transportation IEC 60721-3-2 class 2K3/2K4
Temperature -40...70 °C
Humidity <95% r.h. (non-condensing)
Air pressure. Min. 260 hPa (corresponding to max. 10,000 m
above sea level)
Mechanical conditions IEC 60721-3-2 class 2M2
Reliability
MTBF 24 years
Protection
Housing type IP20 (EN 60529)
Protection class II
Insulation resistance.
Reinforced insulation between relay outputs and
between relay outputs and system electronics
AC 3750 V to EN 60730-1
Standards, guidelines
Product standard EN60730-x
Electromagnetic compatibility (application range) For residential, commercial and industrial environment
EU conformity (CE) CB1T3903xx