Data Sheet for Product

11
Siemens CB1Q3903en
Smart Infrastructure 2020-04-08
Analog outputs (X1…X4)
DC 0…10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA (short-circuit-proof)
DC 4…20 mA output
Resolution 22 μA
Accuracy at 4 mA 150 μA
Accuracy at 12 mA 196 μA
Accuracy at 20 mA 243 μA
DC 0…10 V 4…20 mA
Control of actuators with 0…10V
and 0…20mA analog signals
Analog / digital outputs (X5…X8)
DC 0…10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA (short-circuit-proof)
DC output for off-board loads
Switching voltage DC 24 V
Switching capacity Max. 25 mA
DC 0…10 V
Connecting voltage output and off-board relays to universal I/Os