Data Sheet for Product
5
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Technical data
Power data
Power supply
DC 24 V, G0 (T7)
Operating voltage
DC 24 V ±10 %
Max. power consumption
35 W
Max. external supply line fusing
3 A slow wire fuse or circuit breaker
Outputs
Relay output
Q1 (T10)
Contact
Monostable, NO/NC contact, SPDT
Switching voltage (AC)
AC 24…230 V (-20 %, +10 %)
Switching voltage (DC)
DC 5…30 V
Rated current
AC/DC 4 A (res.), 2 A (cosφ 0.6, ind.),
Min. switching current at AC 19 V
30 mA
Min. switching current at DC 5 V
100 mA
Endurance
100,000 cycles at AC 230 V, 4 A (res.)
Max. external supply line fusing
10 A slow wire fuse or circuit breaker
Relay output
Q2, Q3 (T11) (POL461.45/STD)
Q4 (T11)
Q5, Q6, Q7, Q8, Q9 (T12)
Contact
Monostable, NO contact, SPST
Switching voltage (AC)
AC 24…230 V (-20 %, +10 %)
Switching voltage (DC)
DC 5…30 V
Rated current
AC/DC 3 A (res.), 2 A (cosφ 0.6, ind.)
Min. switching current at AC 19 V
30 mA
Min. switching current at DC 5 V
100 mA