Data Sheet for Product

16
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Battery
Back-up battery
Permissible battery type
BR2032
Operating temperature
-30…80 ℃
Lifetime
Continuous power supply for 1 year
Refer to specifications from battery manufacturer
WARNING
Power off before replacing batteries.
Avoid accidental battery fall out to PCB.
USB
USB stick
Max. capability
32 GB
File system
FAT and FAT32
Function
Download BSP or application
Supported current
100 mA
Supported type
USB 2.0*
Ambient conditions and standards
Ambient conditions and protection classification
Climatic ambient conditions
Transport (packaged for transport) as per
EN 60721-3-2
Temperature: -40...70 °C
Air humidity: < 95 % r.h. (no condensation)
Air pressure: Min. 260 hPa, corresponding to
Max. 10,000 m above sea level
Operation as per EN 60721-3-3.
Temperature -40...70 °C
Restriction process bus -25…70 °C
Air humidity < 95 % r.h. (no condensation).
Air pressure Min. 700 hPa, corresponding to
Max. 3,000 m above sea level
Mechanical ambient conditions
Transport as per EN 60721-3-2
Class 2M2
Degree of protection of housing to EN 60529
IP00
Safety class
Suitable for use in plants with safety class II or class I
Standards, directives and approvals
Product standard
EN 60730-1
Automatic electronic controls for household and similar
use.
Electromagnetic compatibility
(applications)
For residential, commercial, light-industrial and
industrial environments.
EU conformity (CE)
A6V11437166
RCM conformity (EMC)
A6V11437168
UL Listings
UL916, UL60730.
See https://productiq.ulprospector.com/en/
Federal Communications Commission
ICES003
FCC CFR 47 Part 15 Class B
Comply with ICES003 Class B
Environmental compatibility
The product environmental declaration*
)
(A5W90006021) contains data on environmentally
compatible product design and assessments (RoHS