Data Sheet for Product
8
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Configurable inputs and outputs
Configurable inputs
X3, X4 (T3) (POL461.45, POL468.65, POL467.75)
Configurable
By software
Reference potential
Terminals (M)
NTC10k (B
25/85
=3977 K)
Accuracy
Refer to B1…B6
Configurable inputs
X5, X6 (T3) : (POL468.85)
Configurable
By software
Reference potential
Terminals (M)
NTC 100k
Sensor current
96 μA at 25 °C
Range
500 Ω…670 kΩ
Resolution
0.04 - 0.21 k
Accuracy
1.5 K full range; 0.5 K at 10-120 °C
For NTC 100k (B
25/85
=4240 K), refer to below
Temperature
Accuracy
Resolution
-10 °C
0.25
0.06
0 °C
0.14
0.04
20 °C
0.11
0.03
50 °C
0.12
0.03
70 °C
0.15
0.04
90 °C
0.23
0.06