Data Sheet for Product
7
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Inputs
Analog inputs
B1…B6 (T2)
NTC 10k
Sensor current
120 μA at 25 °C
Range
500 Ω…670 kΩ
Resolution
< 44 Ω at 10 kΩ
Accuracy
± 221 Ω at 10 kΩ
For NTC 10k (B
25/85
=3977 K), refer to below
Temperature
Accuracy
Resolution
-10 °C
0.8 K
0.1 K
0 °C
0.3 K
0.1 K
20 °C
0.4 K
0.1 K
50 °C
0.7 K
0.2 K
70 °C
1.3 K
0.3 K
90 °C
2.5 K
0.6 K
Analog inputs
X1, X2 (T3)
Reference potential
Terminals (M)
DC 0…5/0…10 V ratiometric sensor
Resolution
50 mV
Accuracy
100 mV
Input resistance
100 kΩ