Data Sheet for Product
6
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Relay output
Q2, Q3 (T11) (POL461.45/STD)
Q4 (T11)
Q5, Q6, Q7, Q8, Q9 (T12)
Endurance
100,000 cycles at AC 230 V, 3 A (res.)
Max. external supply line fusing F1
6.3 A slow wire fuse or circuit breaker
Relay output
Q2, Q3 (T11) (POL467.75/STD and POL468.65/STD)
Contact
Monostable, NO/NC contact, SPST
Switching voltage (AC)
AC 24…230 V (-20 %, +10 %)
Switching voltage (DC)
DC 5…30 V
Min. switching current at AC 19 V
30mA
Min. switching current at DC 5 V
100mA
Rated current (ind.)
AC/DC 5 A (res.), 4 A (cosφ 0.6, ind.)
Endurance
100,000 cycles @ AC 230 V, 5 A (res.)
Max. external supply line fusing
10 A circuit breaker
Triac output
Q6, Q7 (T12) (POL467.75/STD)
Switching voltage
AC 24…230 V (-20 %, +10 %)
Switching capacity
Max. 500 mA
Min. 10 mA