Data Sheet for Product

20
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
POL461.45/STD
POL468.xx/STD
POL467.75/STD
① Five screws (GB818-M3.5×8) and
five washers (⌀ 4)
② Five standoffs M3.5×L (L>10 mm)
① Seven screws (GB818-M3.5×8)
and seven washers (⌀ 4)
② Seven standoffs M3.5×L
(L>10 mm)
① Seven screws (GB818-M3.5×8)
and seven washers (⌀ 4)
② Seven standoffs M3.5×L
(L>10 mm)
Note: Mounting screws and washers are not included in the delivery package.
WARNING
Always mount the controller with insulation washers.
Accidental fall-out of metallic screws may cause a short circuit.
Notice
Take appropriate measures to prevent against static electricity (e.g. use a grounding strap) when mounting the
controller.
Engineering
On voltages above 42 Veff, the device must be installed in an enclosure to protect
against accidental contact with relay connections. A key or tool is required to open the
enclosure.
AC 115…230 V cables must be double-insulated against safety extra-low voltage (SELV)
cables
Do NOT mix SELV / PELV and mains power on the same terminal block. Use external
protection for inductive loads of relay outputs
Use external fuse for over-current protection of relay and triac outputs
Use an ESD protected manufacturing environment (PCB only, no housing)
Avoid negative voltage on analogue inputs since the measured ADC values are
undefined. The accuracy of the 10 V analog inputs is valid for values above 100 mV.
Make sure the device is powered with DC 24 V (AC may damage the device)
Maintenance
To prevent from possible damage from static electricity, take necessary measures (e.g. use
a grounding strap) when mounting the controller.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.