User Manual
9
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
DC 0…5/0…10 V input
Ratio-metric sensors
Resolution
50 mV
Accuracy
100 mV
Input resistance
33 K
Configurable outputs
X5, X6, X7 (T4) (POL461.45/STD)
X5, X6, X7, X8 (T4) (POL468.65/STD)
X7, X8 (T4) (POL468.85/STD)
X5, X6, X7, X8, X9 (T4) (POL467.75/STD)
Configurable
By software
Reference potential
Terminals (M)
DC 0…10 V output
Resolution
30 mV
Accuracy
100 mV
Output current
Max. 1 mA
PWM output
Frequency
500…2.5 kHz
Duty cycle
10…90 % (at an increment of 0.5 %)
Max. current
10 mA
Signal amplitude
10 V
Digital input
D1, D2 (T5)
Configurable
By software
Potential free (Fast DI)
Active DI AC 24V
Active DI DC 24V (Fast DI)
POL461.45, POL468.65, POL467.75
POL468.85 only
POL468.85 only
0/1 digital signal (binary)
For potential free contacts
Sampling voltage/current
DC 24 V
Contact resistance
Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 20 Hz