Climatix 46X variants list
Hardware I/Os
POL461.45/
STD
POL468.65/
STD
POL468.85/
STD
POL467.75/
STD
Analog inputs
B1…B6
NTC 10 k
✓
✓
✓
✓
Configurable
inputs
X1, X2
DC 0…10 V or 0…5 V
✓
✓
✓
✓
X3, X4
NTC 10 k, DC 0…10 V
✓
✓
✓
✓
X5, X6
NTC 100 k, DC: 0…10 V/0…5 V
✓
Digital inputs
D1, D2
Potential free (Fast DI)
✓
✓
✓
Active DI 24 AC/DC (Fast DI only with DC)
✓
D3, D4, D5
potential free
✓
✓
✓
D3, D4, D5
active AC/DC 24 V
✓
D6
potential free
✓
DL1
active AC 115….230 V
✓
✓
✓
Configurable
outputs
X5, X6
DC 0…10 V analog/PWM output
✓
✓
✓
X7, X8
DC 0…10 V analog/PWM output
✓
✓
✓
X9
(DC 0…10 V analog/PWM output)
✓
Digital outputs
Q1
relay output
✓
✓
✓
✓
Q2…Q5
✓
✓
✓
✓
Q6, Q7
✓
✓
✓
Q8, Q9
✓
✓
✓
✓
Q6, Q7
triac output
✓
Interfaces
RS485 interface (Modbus RTU or BACnet MSTP)
✓
✓
✓
✓
USB interface
✓
✓
✓
✓
Local service interface
✓
✓
✓
✓
EEV
2
2
2
0
Extension interface (RS485)
✓
✓
✓
✓
Ethernet port
✓
✓
✓
M-Bus interface
✓