User Manual
14
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
Tool
USB
Use PC service cable POL0C2.40/STD for tools
Ethernet TCP/IP port (T-ETHERNET)
POL467.75/STD and POL468.65/STD
Plug
RJ45
Interface type
10 base-T and 100 base-TX, IEEE802.3 compatible
Bitrates
10/100 Mbps Auto sensing
Multiple connections
Possible when use HUB or switch
Ethernet cable
CAT5 shielded twisted pair
Engineering and commissioning
Sapro and Scope tool
Cloud services
Climatix IC
Integration
Modbus TCP/IP, BACnet IP(B-ASC)
BACnet/IP interface
Supports B-ASC profile
M-Bus (T8)
POL467.75/STD only
Mode
M-bus master
Bus connection terminals
CM+, CM- (interchangeable)
Bus cable
2-wire, telephone cable (JYStY N*2*0.8 mm)
Bus connection/electronics
Galvanically isolated
Bus voltage
DC 28 V (short-circuit-proof)
Bus length
Max. 50 m
Number of bus devices (standard load 1.5 mA)
Max. 3
Cable types, bus topology, bus termination
Refer to M-bus norm DIN EN 13757
Baud rate
300, 2400
Supported data structures
See basic documentation A6V11276161
LEDs
LED for BSP run/stop
Color
Flash response
Function
Red/green
Changes at 1 Hz
Software update mode:
Download application or new firmware
Green
Continuous
Application loaded and is running
Orange
Continuous
Application loaded but is not running
Orange
Flashing, 50 ms on/1000 ms off
Application not loaded
Red
Flashing at 2 Hz
Firmware error
Red
Continuous
Hardware fault