User Manual

12
Siemens
A6V11276159_en--_c
Smart Infrastructure
2020-09-25
WARNING
The relay circuits have no internal fuse. An external supply line fuse is required (for fuse
set of Q2 and Q3, refer to basic documentation A6V11276161).
Do NOT mix SELV / PELV and mains power on the same terminal block.
Use external protection for inductive load.
Avoid negative voltages at the analog inputs since conversion leads to undetermined
results.
Maintain clearing distance of 6.4mm between SELV/PELV and mains power when
different terminal blocks are used.
EEV
EEV (T8, T9) (POL461.45/STD, POL468.65/STD and POL468.85/STD)
Configurable
By software
Connector
B6B-XH-A, JST
Stepper motor drive
(Assembled in POL461.45 POL468.65 and POL468.85)
Motor
Unipolar stepper motor, full step or half step
DC 12 V, Max. 2 x 260 mA per EEV
Connection
5/6 wires
Supply voltage
DC 12 V (short circuit protected)
Current limitation
Max.260 mA per phase EEV (both EEV1 and EEV2 are
operating at the same time)
Max.375 mA per phase EEV (both EEV1 and EEV2 are
not operating at the same time)
Driver output
4 channels
Length of motor cable
< 3 m