User Manual
Communication
Ethernet TCP/IP port
6
A6V1127616_en--_a 35 | 38
3. Define M-bus mapping in SCOPE
4. Load the M-bus mapping file to the controller (OBHcomp.UCF file)
Note:
An example of Sapro application can be downloaded from the SIOS (
https://support.industry.siemens.com/cs/ww/en/view/109768481 ). This application
shows the integration of 2 M-bus meters via primary addressing to a POL467
controller including the M-bus mapping of the bindings.
More details on M-bus engineering is available in the SAPRO Online Help.
6.5 Ethernet TCP/IP port
POL467 and POL468 have Ethernet interface 10/100 Mbps (IEEE 802.3U).
Connectable devices
The Ethernet interface supports below functions:
● PC tools (SCOPE)
● HMI@Web (Web browser)
● Climatix IC
● Modbus TCP/IP
● BACnet IP
● Climatix touch panels
Note: maximum 3 clients and protocols are supported at the same time.
Set TCP/IP parameter
The TCP/IP parameters, such as IP address must be set up via SCOPE or HMI
DM/TM.
The system object “IP-config” can set up all TCP/IP parameters.
Note: Default value for “DHCP” is “Active”. If there is no DHCP server in the
network, the IP address of the controller is illegal as “169.254.XXX.XXX”.