User Manual
Communication
Local service interface
6
A6V1127616_en--_a 33 | 38
Connecting PC tools
The connection to PC tools such as SCOPE, PC USB port and cable type
POL0C2.40/STD is as follows:
Connecting touch panel
C400 controllers can be connected with touch panels using Modbus over RS485
as follows:
Limitations
● Maximum length of unshielded twisted pair cable is 3 m
● P2P communication is preferable to the RS485 network
Cable connection
The top view of RJ45 jack (8 pins) is as follows:
Pin-out for RJ45-connector
Pin Signal
1 USB device, D+
2 USB device, D-
3 RS485, A+
4 Ground
5 Select 2
6 RS485, B-
7 Select 1
8 DC 24 V (output)
Note:
● Maximum current at DC 24 V is 60 mA, only powered for HMI DM/TM.
● Default setting for this interface is Modbus slave. It can be configured to
Modbus master mode.