User Manual

Hardware IO connect
ion
Relay outputs
4
18 | 38 A6V1127616_en--_a
For POL461, the rated current for Q2 and Q3 is 3 A. use a 6.3 A fuse to protect the
controller from overheating.
For POL467 and POL468, the rated current for Q2 and Q3 is 5 A and is designed
to withstand high inrush current (7 to10 times of the rated current, for example
capacity load 40 A (100 us) ).
As a result, terminals Q2 and Q3 on POL467/468 can drive high efficiency devices
such as a pump or compressor within the specified rated current range.
If Q2 and Q3 are used to drive high current devices, and Q4 is not powered
from the common of T11, a 10 A fuse can be used to protect the controller from
overheating.
If Q4 is connected to the common of T11, the fuse F1 needs to be derated to
6.3 A to prevent the controller from overheating as Q4 is rated 3 A. In this case,
the Q2/Q3 should drive high-load devices with and external relay.
We recommend to use varistors (MOV) or RC absorbers to protect devices or
individual relays with high capacitive or inductive loads connected to Q2 and
Q3. See the example below.
WARNING
Do not mix SELV/PELV and line voltage on the same terminal.
Any compressor circuit, interference suppression, etc. must be provided
externally per the application.
The indicated fuse rating does protect the controller from overheating and
burning in case of a failure. In such a fault condition, a relay might be
destroyed whereas the controller remains protected from entering a
dangerous condition. To protect the individual relays or connected devices,
other measures must be considered.
Outputs must be separately fused if the connected loads are to be protected
or the common fuse needs derating.
Use external protection for inductive load.
AC 115/230 V cabling must have double insulation against cables carrying
safety extra
-
low voltage (SELV). The cables must be fixed by strain reliefs.