User Manual

9
Siemens AG
A6V11185116_en_a
Building Technologies 2017-08-11
Configurable outputs
X3, X4 (T2), X5(T3)
Configurable By software
Reference potential Terminals
DC 0…10 V output
Resolution 30 mV
Accuracy 100 mV
Output current max. 10 mA
PWM outputs
Frequency 2.5 kHz
Duty cycle 0...100% (at an increment of 0.5%)
Max. current 10 mA
Signal amplitude 10 V
Digital inputs
DI1, DI2 (T4)
0/1digital signal (binary) For potential free contacts
Sampling voltage/current DC 24 V, 12 mA
Contact resistance max. 200 Ω (closed)
min. 50 kΩ (open)
Delay 10 ms
Pulse frequency max. 20 Hz