User Manual

7
Siemens AG
A6V11185116_en_a
Building Technologies 2017-08-11
Triac outputs
DO1, DO2 (T11)
Triac data
Switching voltage AC 24…230 V (-20%, +10%)
Switching capacity max. 500 mA / min. 10 mA
Max. external supply line fusing 2.0 A, slow wire fuse or circuit breaker
WARNING
Do NOT mix SELV / PELV and line voltage on the same terminal.
Use external protection for inductive load.
Analog inputs
B1…B3 (T1)
PT1000
Temperature range -50…150 °C