User Manual
6
Siemens AG
A6V11185116_en_a
Building Technologies 2017-08-11
Relay output
Q3, Q4 (T9)
Q5, Q6 (T10)
Contact Monostable, NO contact, SPST
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res./ind.) AC 3 A (res.)/2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current @ AC 19 V 30 mA
Endurance 100’000 cycles @ AC 230 V, 3.0 A (res.)
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
WARNING
Do NOT mix SELV / PELV and line voltage on the same t
erminal.
Use external protection for inductive load.