Technical data
Power supply
AC 24 V, G0 (T7)
Operating voltage AC 24 V ±20% / DC 24 V ±10%
Frequency 45…65 Hz @ AC 24 V
Max. AC current 1.1 A @ AC 24 V
Max. DC current 1.0 A @ DC 24 V
Max. external supply line fusing 3 A slow wire fuse or circuit breaker
Relay output
Q1 (T8)
Contact Monostable, NO/NC contact, SPDT
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res./ind.) AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V 30 mA
Endurance 100’000 cycles @ AC 230 V, 3.0 A (res.)
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
WARNING
Do NOT mix SELV / PELV and line voltage on the s
ame terminal.
Use external protection for inductive load.