User Manual
4
Siemens AG
A6V11185116_en_a
Building Technologies 2017-08-11
Notes
Engineeri
ng
● In order to protect against accidental contact with relay connections at voltages above 42
Veff, the device must be installed in an enclosure (preferably a control panel). It must be
impossible to open the enclosure without the aid of a key or tool.
● AC 115…230 V cables must be double-insulated against safety extra-low voltage (SELV)
cables.
● Do NOT mix SELV / PELV and line voltage on the same terminal.
● Use external protection for inductive load of relay outputs.
● Use external fuse for over current protection of relay and triac outputs.
● Avoid negative voltage on analogue inputs, because the measured ADC values are
undefined. The accuracy of the 10 V analogue inputs is valid for values above 100 mV.
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.