User Manual
15
Siemens AG
A6V11185116_en_a
Building Technologies 2017-08-11
Climatix controller
Hardware I/Os POL427.50
Analog inputs B1, B2, B3 (PT1000) ✓
Configurable inputs
X1, X2, X6 , X7
(PT1000 / NTC 10k / NTC 1k / LG-Ni1000 /
DC 0…10 V/ DI)
✓
Digital inputs X8 (binary/high speed) ✓
D1, D2 (binary) ✓
DL1 (active AC 115…230 V) ✓
Configurable
outputs
X3, X4, X5
(DC 0...10 V analog output / PWM output)
✓
Digital outputs Q1, Q3, Q4, Q5, Q6 (relay output) ✓
DO1, DO2 (triac output) ✓
Interfaces Process bus interface ✓
Modbus RTU or BACnet MS/TP ✓
SD card interface ✓
Local service interface ✓
M-Bus Master for up to 3 slaves ✓