Digital input
X8 (T3)
Configurable By software
0/1 digital signal (binary) For potential free contacts
Sampling voltage/current DC 21.2 V, 8 mA
Contact resistance max. 200 Ω (closed)
min. 50 kΩ (open)
Delay 10 ms
Pulse frequency max. 300 Hz
Pulse measurement
Sensor Open-collector
Sampling voltage DC 21.2 V, 8 mA
Max. speed 18000 RPM
Min. ON/OFF time 500 µs
Powering sensors
Active
DC 24 V (T2)
Voltage/current DC 24 V (±10 %), 40 mA
Reference potential Terminals ┴