Data Sheet for Product
9 / 22
Siemens Climatix controller POL424.70/STD A6V10421228_en--_c
Smart Infrastructure 2021-09-10
Disposal
The devices are considered electronics devices for disposal in accordance with the
European Guidelines and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage AC 24 V ±20% / DC 24 V ±10%
Frequency 45…65 Hz at AC 24 V
Max. AC current 1.1 A at AC 24 V
Max. DC current 1.0 A at DC 24 V
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
Relay
Contact Monostable, NO / NC contact, SPDT
Switching voltage AC 24…230 V (-20%, +10%)
DC 18…30 V
Rated current (res. / ind.) AC 3 A (res.) / 2 A (ind. cosφ 0.6)
DC 3 A (res.)
Min. switching current at AC 19 V 30 mA
Endurance 100,000 cycles at AC 230 V, 3.0 A (res.)
Max. external supply line fusing 6.3 A slow wire fuse or circuit breaker
Do not mix SELV / PELV
and line voltage on the
same terminal.
Use external protection for
inductive load.
Power supply
AC 24 V, G0 (T7)
Relay output
Q1 (T8)